Omnes Categoriae
Dc reactor
Domum> Dc reactor

Dc Reactor Reactor Lævigator

Parametri technici
Voltagium operationis ratum: 380V-1140V/50Hz
2. Currentio operationis ratus: 3A ad 2000A/40℃
3. Fortitudo electrica: Nullus disruptio arcus in 3000VAC/50Hz/5mA/10s pro nucleo et involucro
4. Resistenta izolării: valoarea rezistenței de izolare a surselor de 1000VDC este ≥100MΩ
5. Zgomot al reactorului: mai mic de 65dB (testat la o distanță orizontală de 1 metru de la reactor)
6. Grad de protecție: IP00
7. Clasa de izolare: clasa F sau mai sus

Introductio

Rerum Technicarum Summarium Reactoris DC (Reactor Laevigandi)

Functiones Principales

Compression Harmonica: Finit undulationem AC (20-150Hz) in parte DC (typicum ≤10% a cursu praefinito).

Melioratio Factoris Potentiae: Augeit input PF ab 0.75 ad 0.95 (operatione 50Hz).

Continuitas Cursus: Servat minimum cursum criticum ne rectificator interruptus fiat.

Specificationes Claves

Inductio: 1–30 mH (varies cum gradu potentiae inverteris)

Gradus Curretis: 100–3000 A

Decessio Voltii: <2% voltii accepti

Application missiones

Classis A (Installatio Obligatoria):

Reticulum THDv >5% aut capacitas brevis circui >40× gradum inverteris

Systemata multi-inversoria parallela (≥3 unitates)

Classis B (Installatio Recommandata):

Transformator capacitas >10× gradus inverter (impedimentum <4%)

Ratiocinatio inaequalitatis voltatium: 1.8–3%

Classis C (Installatio Optionalis):

Systemata cum compensatione potentiae reactivae (antiresonantia necessaria)

Alimenta funicularia longa (>100 m)

Installation Guidelines

Distancia ad inverterem: <5 m (ad minimas effectus inductantiae lineae)

Spatium a capacitoribus: ≥3× longitudinem apparatus

Optimanda sunt pro frequentia commutationis IGBT (typice 2–8 kHz)

Caracteristicae Protectionis

SensOREs interni temperatura (85°C alarmum, 105°C excursio)

Classis isolationis: F (155°C)

Formula dimensionANDi: L min = (2π⋅f⋅ΔIΔU)⋅K (ΔU: voltagium fluctuationis permittendum, f: frequentia fluctuationis, ΔI: currus fluctuationis permittendus, K: factor securitatis 1.2–1.5)

Prospectus operationis:

Diminuit currentem harmonicum input per 40–60%

Diminuit amissos thermicos condensatoris per 15–25%

Conformis normis IEEE 519-2014 pro mitigatione harmonicarum.

Plura producta

  • Temperatus Controller aridi LD-B10-10F

    Temperatus Controller aridi LD-B10-10F

  • BWDK-3206H Temperature Controller siccae BWDK-3206H

    BWDK-3206H Temperature Controller siccae BWDK-3206H

  • BWDK-3206A Temperature Controller siccae BWDK-3206A

    BWDK-3206A Temperature Controller siccae BWDK-3206A

  • LD-B10-220 Temperature Controllerem aridae LD-B10-220

    LD-B10-220 Temperature Controllerem aridae LD-B10-220

Accipe Citatum Gratuito

Noster legatus cito te continebit.
Email
Nomen
Company Name
Missiva
0/1000